Watts 009M2 Reduced Pressure Zone Backflow Preventer (Model 0063010) Instruction Manual

For Models: 009M2, 009M2-QT

1. ভূমিকা

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. গুরুত্বপূর্ণ নিরাপত্তা তথ্য

3. পণ্য শেষview এবং উপাদান

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. সেটআপ এবং ইনস্টলেশন

  1. প্রাক-ইনস্টলেশন চেক:
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • কোনও শিপিং ক্ষতির জন্য ইউনিটটি পরীক্ষা করুন।
    • Ensure all necessary tools and materials for installation are available.
  2. সাইট প্রস্তুতি:
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. পাইপিং সংযোগ:
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. পোস্ট-ইনস্টলেশন চেক:
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • ফাঁসের জন্য সমস্ত সংযোগ পরিদর্শন করুন।
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. অপারেটিং নির্দেশাবলী

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

6. রক্ষণাবেক্ষণ

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

7. সমস্যা সমাধান

সমস্যাসম্ভাব্য কারণসমাধান
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
জল প্রবাহ নেই বা প্রবাহ কমে গেছে
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Ensure shutoff valves are fully open.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
সংযোগ থেকে লিক
  • Improperly sealed threads
  • Damaged gaskets
  • Re-apply thread sealant and tighten connections.
  • গ্যাসকেটগুলি পরীক্ষা করুন এবং প্রতিস্থাপন করুন।

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. স্পেসিফিকেশন

মডেল নম্বর0063010 (009M2)
Backflow Preventer Typeচাপ জোন সমাবেশ হ্রাস
শরীরের উপাদানব্রোঞ্জ
ইনলেট/আউটলেট সংযোগের আকার2 Inches (50 MM)
Inlet/Outlet Connection TypeFemale Threaded NPT
সর্বোচ্চ কাজের চাপ175 পিএসআই (12.10 বার)
সর্বোচ্চ তাপমাত্রা180°F (82°C)
নূন্যতম তাপমাত্রা33°F (0.5°C)
সুরক্ষা প্রকারBackpressure and Backsiphonage
পণ্যের মাত্রা (L x W x H)22 x 10 x 8 ইঞ্চি
আইটেম ওজন27 পাউন্ড
Lead Free StatusNO (For non-potable use only)